Description
Overview
Essential details:HID2030SK Pepperl+Fuchs SMART Transmitter Power Supply
< 2-channel isolated barrier
< 24 V DC supply (bus powered)
< 2-wire SMART transmitters or current sources
< Usable as signal splitter (1 input and 2 outputs)
< Dual output 4 mA … 20 mA, current sink
< Line fault detection (LFD)
< Up to SIL 2 (SC 3) acc. to IEC/EN 61508
This isolated barrier is used for intrinsic safety applications. It provides a fully floating supply to power 2-wire SMART transmitters in the hazardous
area, and repeats the current to drive a safe area load. It is also used with 2-wire current sources. It is designed to provide a sink mode output on
the safe area terminals.
Digital signals may be superimposed on the analog values in the hazardous or safe area, which are transferred bidirectionally.
A separate fault output on the bus is signaled if the input signal is outside the range 0.2 mA … 24 mA. The fault conditions can be monitored via a
Fault Indication Board.
This module mounts on a HiD Termination Board.
lf you need to inquire or purchase ,please send the product models to my email or call medirectly .
sunny He
[Email] sales@xiongbagk.cn
[Mobile] 86-18059884797
[WhatsApp] 86-18059884797
[Skype] sales@saulcontrol.com
HID2030SK Pepperl+Fuchs SMART Transmitter Power Supply
• Communication for SMART transmitter is provided only on output channel 1.
• Minimum supply voltage available for field transmitters is 14.7 V at 20 mA.
• Safety parameters are now:
– Uo = 27.2 V
– Io = 93 mA
– Po = 633 mW
• See operating instructions for other connection options and for more details.