The 760-P5-G5-S5-HI-A20-R-T is a GE Multilin protective relay. This relay is a feeder management relay designed with 5 A phase current inputs, 5 A zero sequence current inputs, and 5 A sensitive ground current input. This contrasts with other units in the series that may accept inputs of 1A, 10A, 20A, or some combination, so users should make sure they are buying the unit appropriate to their system’s needs. The unit can be mounted on a 19-inch panel, and Multilin’s 1601-0120-AE manual can provide further in-depth assistance on how to get the unit up and running.

Categories: ,

Description

Overview


Essential details:760-P5-G5-S5-HI-A20-R Multilin protective relay

760-P5-G5-S5-HI-A20-R-T Technical Specifications

Ambient Storage Temperature Range -40°F to +176°F
Analog Input Conversion Range 0 to 21 mA
Communications Baud Rate 300 to 19200 baud
Features Red Breaker Closed LED, Ethernet, Enhanced Faceplate
Operating Temperature Range -40°F to +140°F
Pollution Degree II
Relay Dimensions approx. 18cm W, 16.5cm L, 21.5cm H

Product Description

The 760-P5-G5-S5-HI-A20-R-T is a GE Multilin protective relay. This relay is a feeder management relay designed with 5 A phase current inputs, 5 A zero sequence current inputs, and 5 A sensitive ground current input. This contrasts with other units in the series that may accept inputs of 1A, 10A, 20A, or some combination, so users should make sure they are buying the unit appropriate to their system’s needs. The unit can be mounted on a 19-inch panel, and Multilin’s 1601-0120-AE manual can provide further in-depth assistance on how to get the unit up and running.

The 760-P5-G5-S5-HI-A20-R-T GE Multilin relay offers a  power supply rated at 88-300 VCD, 70-265 VAC @ 48-62 Hz. The unit has Eight 4-20 mA analog outputs. This unit includes a Red breaker closed LED and includes an enhanced display with Ethernet 10Base T option. The enhanced faceplate boasts a wider LCD and cleaner design. The Ethernet 10Base T option allows the relay to connect to a larger network and be interacted with remotely.

The 760-P5-G5-S5-HI-A20-R-T possesses a number of monitoring capabilities such as data logging, oscillography, waveform capture, and actual value metering. Relay users can check some of this data through the unit’s 40-character alphanumeric liquid-crystal display, or use GE Multilin’s EnerVista 760 software program which provides a more streamlined and expansive user interface. Data recorded by the relay can be trended, graphed, and exported for further review.

750-P5-G5-D5-HI-A20-R750-P5-G5-D5-HI-A20-R750-P5-G5-D5-HI-A20-R750-P5-G5-D5-HI-A20-R

lf you need to inquire or purchase ,please send the product models to my email or call medirectly .

sunny  He

[Email] sales@saulcontrol.com

[Mobile] 86-18059884797

[WhatsApp] 86-18059884797

[Skype] sales@saulcontrol.com

760-P5-G5-S5-HI-A20-R Multilin protective relay

Frequently Asked Questions about 760-P5-G5-S5-HI-A20-R-T

What are the analog input terminals positive A1 and negative A2 provided for on the GE Feeder Management Relay 760-P5-G5-S5-HI-A20-R-T?
The analog input terminals A1 and A2 for the GE Relay 760-P5-G5-S5-HI-A20-R-T are there for the input of current signals from a lot of different transducer outputs, like the transformer tap position, transformer winding temperature, the battery and bus voltage, or the station service voltage.
How many output analog channels does the 760-P5-G5-S5-HI-A20-R-T GE Feeder managment Relay provide?
All the 750/760 GE Feeder Management Relay’s have eight available output analog channels which has a full range scale. But each output analog channel can be one of the parameters that are measured by the relay by reprogramming the analog output channels.
From the typical wiring diagram, which terminals for the analog output signals are originated the GE Feeder Management Relay 760-P5-G5-S5-HI-A20-R-T?
Terminals A5 through A12 are the terminals that are originated to the analog output signals, and they also share A4 in a return that is very common. There are different ground potential outputs signals that are on the inside and are isolated but they allow connections to those ground devices.