Essential details:RED670 Substation Automation Products Line
lf you need to inquire or purchase ,please send the product models to my email or call medirectly .
sunny He
[Email] sales@saulcontrol.com
[Mobile]Â 86-18059884797
[WhatsApp] 86-18059884797
[Skype] sales@saulcontrol.com
RED670 Substation Automation Products Line
When a small transformer is connected as a tap on the line, the line differential protection can be used without having an additional RED670 installed at the transformer tap. For low fault currents behind the tap transformer the line differential protection of RED670 includes a useful definite time or inverse time delayed characteristic. This enables selective operation of other protection functions located at the tapped transformer’s high or low voltage side.
Extensive built-in protection for lines and cables
The RED670 features integrated distance protection to ensure fault clearance in case of communication failure. The full scheme distance protection provides independent phase selection, power swing detection and a wide range of scheme communication logics. The four-zone distance protection is further enhanced with load encroachment, which increases the ability to detect high resistive faults on heavily loaded lines.
You can increase the functionality of your RED670 IEDs with optional back-up and multipurpose protection functions. Versatile overcurrent and thermal overload functions provide additional back-up protection. Breaker failure protection allows high speed back-up tripping of surrounding breakers and re-tripping of the own breaker, for instance, to avoid