REX010 HESG324426R0001 Injection unit

REX010 HESG324426R0001 Injection unit

The earth fault protection is based on the injection of a coded signal. The resulting offset voltage is utilized to calculate the earth resistance (Rf).
The injection signal is produced in the injection unit REX010 and applied to the generator through the transformer unit REX011. For the coupling to the protected unit resistors (RE, RP) are used. For the rotor earth fault protection two capacitors are required in addition.

Categories: ,

Description

Overview


Essential details:REX010 HESG324426R0001 Injection unit

The earth fault protection is based on the injection of a coded signal. The resulting offset voltage is utilized to calculate the earth resistance (Rf).
The injection signal is produced in the injection unit REX010 and applied to the generator through the transformer unit REX011. For the coupling to the protected unit resistors (RE, RP) are used. For the rotor earth fault protection two capacitors are required in addition.
The measurement signals for earth fault protection are processed by the REG216 or the REG316*4 respectively.
The equipment described protects 100% of the generator stator winding. Two independent protection functions are applied: one for 95% and one, using a different algorithm, for 100% of the stator winding. The 100% function is calculating the earth resistance and the 95% function is measuring the neutral voltage displacement of the generator.
a) The 100% function protects 35% of the stator windings from the neutral point for Rf = 0 and I0max = 15 A
b) The 95% function (U>) protects 95% of the generator stator winding from the terminals. This results in an overlap
(redundancy) of the two protection functions as seen in Fig. 1.
The 100% function increases in sensitivity with increasing earth fault resistance and decreasing earth fault current.

REX010

lf you need to inquire or purchase ,please send the product models to my email or call medirectly .

sunny  He

[Email] sales@saulcontrol.com

[Mobile] 86-18059884797

[WhatsApp] 86-18059884797

[Skype] sales@saulcontrol.com

REX010 HESG324426R0001 Injection unit

The protection equipment consists of the following units (Figures 4 – 8): REG216/316*4: Numerical generator protection REX010: Injection unit
REX011: Injection transformer unit with auxiliary contactor In addition the following components are required:
– Earthing resistors in the generator neutral point (REs, RPs) and in the excitation circuit (REr, RPr)
– Coupling capacitors in the excitation circuit of the rotor
– Voltage transformers
The injection unit (REX010) together with the injection transformer (REX011) produces three coded square wave signals (Uis, Uir, Ui) with a frequency fN/4. These square wave signals are injected into the protected object via the coupling components. The three square waves have different amplitudes: Uis (Injection signal for the stator), Uir (Injection signal for the rotor) and Ui (reference signal for the REG216/316*4). The injection unit REX010 is connected to the station battery and the injection signal voltage is generated either by the battery or by an internal DC/DC converter.