DVC2000 30MA-30VDC-100PSI MAX Digital Valve Controller
Restart Control Mode
Restart Control Mode (Restart Cont Mode) lets you choose which operating mode you want the instrument to be in after a restart. Follow the prompts on the handheld communicator display to define the restart control mode as Resume Last, Analog, or Digital.
Restarting the Instrument
Restart resets the instrument in the same manner as when power to the instrument is interrupted. When Restart is issued, all of the newly entered configuration variables become active. Otherwise, they may not take effect until the instrument is placed In Service.
Burst Mode
Enabling burst mode provides continuous communication from the digital valve controller. Burst mode applies only to the transmission of burst mode data (analog input, travel target, pressure, and travel) and does not affect the way other data is accessed.
Access to information in the instrument is normally obtained through the poll/response of HART communication. A handheld communicator or control system may request any of the information that is normally available, even while the instrument is in burst mode. Between each burst mode transmission sent by the instrument, a short pause allows the handheld communicator or control system to initiate a request. The instrument receives the request, processes the response message, and then continues “bursting” the burst mode data.
There are four burst mode commands. Command 3 is recommended for use with the Rosemount™ 333 HART Tri-Loop™ HART-to-analog signal converter. The other three are not used at this time.
Command 3 provides the following variables:
Primary variable—analog input in % or mA,
Secondary variable—travel target (valve set point) in % of ranged travel,
Tertiary variable—output pressure in psig, bar, or kPa,
Quaternary variable—travel in % of ranged travel.
To enable burst mode select Mode > Burst > Burst Enable. To send a burst mode command, select Burst Command. Burst mode must be enabled before you can change the burst mode command.