560CVT10 Current/Voltage Transducer Interface
The fault current is measured up to 20 times nominal current. Therefore the current inputs withstand 50 times nominal current for 1 s.
The CT/VT interface is equipped with one binary output which can be used to indicate e.g. alarm for over current.
All CT/VT interfaces are mounted in the RTU cabinet. Current and voltage inputs are connected via transformer only (see Figure 1).
The CT/VT interfaces are designed for mounting on DIN rails 35 mm.
Meter Operation
The following metered parameters are available:
Instantaneous Meter Values
Measured by true RMS conversion and transmission to the RTU560 of following values:
x Phase – Neutral Voltage 1N, 2N, 3N, Average
x Phase -Phase Voltage 1-2, 2-3, 3-1, Average
x Current Phase 1, 2, 3
x Fault Current Phase 1, 2, 3, N
x Active Power, Phase 1, 2, 3, Total
x Reactive Power, Phase 1, 2, 3, Total
x Apparent Power, Phase 1, 2, 3, Total
x Power Factor, Phase 1, 2, 3, Average
x Frequency,
x Phase Rotation
x Voltage / Current Harmonic Distortion (THD,
current and voltage phase 1,2 and 3)
Derived Meter Values
x calculation of Active, Apparent and Reactive Energy accumulated values (intermediate and end of period readings, delivery and consumption)
x calculation of Ampere Hours accumulated values (intermediate and end of period readings, delivery and consumption)
x Neutral current (with 3 wire connection)