Description
Overview
Essential details:REF615C_C HCFFAEAGANB2BAN1XC Feeder Protection and Control
lf you need to inquire or purchase ,please send the product models to my email or call medirectly .
sunny He
[Email] sales@xiongbagk.cn
[Mobile] 86-18059884797
[WhatsApp] 86-18059884797
[Skype] sales@saulcontrol.com
REF615C_C HCFFAEAGANB2BAN1XC Feeder Protection and Control
The IED offers directional and non-directional overcurrent and thermal overload protection as well as directional and non-directional earth-fault protection. Some standard configurations allow as an option admittance-based, harmonics-based or wattmetric-based earth-fault protection to be used in addition to directional earth-fault protection. Further, the IED features sensitive earth-fault protection, phase discontinuity protection, transient/intermittent earth-fault protection, overvoltage and undervoltage protection, residual overvoltage protection, positive-sequence undervoltage and negativesequence overvoltage protection. Frequency protection, including overfrequency, underfrequency and frequency rate-of-change protection, is offered in IEDs with standard configurations H and J. The IED also incorporates optional three-pole multi-shot auto-reclose functions for overhead line feeders.
Enhanced with optional hardware and software, the IED also features three light detection channels for arc fault protection of the circuit breaker, busbar and cable compartment of metalenclosed indoor switchgear.