Sale!

VME-PROF-S PROFIBUS with PROFIBUS-DP-Slave state

The DMS device does meet all EMV requirements under the following conditions:
1. The device is operated in a DMS rack with CE certification. All devices of a VMEbus system need to comply with the EU guidelines on electromagnetic compatibility (#89/336/EWG) (i.e. must feature a CE symbol).
2. The VMEbus-system frame ground must be connected to the system ground through a low resistance cable.
3. PROFIBUS systems must employ cables and connectors that are recommended by DMS or that are compatible with those recommended by DMS (see Chapter 3.2.1.1).
4. Shielded Cables are to be used for all additional data connections. All connectors (jacks, sockets, and plugs) must be fitted with a metal shielding. The protective case must be connected bidirectionally conducting with the cable shielding. In order to prevent transient currents within the GND shielding, the potential drop needs to be compensated for by means of bonding.

Categories: ,

Description

Overview


Essential details:VME-PROF-S PROFIBUS with PROFIBUS-DP-Slave state

The DMS device does meet all EMV requirements under the following conditions:
1. The device is operated in a DMS rack with CE certification. All devices of a VMEbus system need to comply with the EU guidelines on electromagnetic compatibility (#89/336/EWG) (i.e. must feature a CE symbol).
2. The VMEbus-system frame ground must be connected to the system ground through a low resistance cable.
3. PROFIBUS systems must employ cables and connectors that are recommended by DMS or that are compatible with those recommended by DMS (see Chapter 3.2.1.1).
4. Shielded Cables are to be used for all additional data connections. All connectors (jacks, sockets, and plugs) must be fitted with a metal shielding. The protective case must be connected bidirectionally conducting with the cable shielding. In order to prevent transient currents within the GND shielding, the potential drop needs to be compensated for by means of bonding.
5. Data cables must not be installed near the mains lead or near cables with a high throughput or switching high inductance loads.
6. When installed outdoors all cables that may be subjected to excessive voltages (e.g. lightning) are to be fitted with lightning arresters or to be protected by metal tubes.
7. All slots of a system rack that are not currently in use need to be closed by an electrically conducting front panel.
8. During operation and installation of the device – special care is required with respect to electrostatic discharge (ESD – see also EN 10015-1 Basic Specification: Protection of electrostatic sensitive devices).

The VME-PROF-S is a compete independent PROFIBUS-DP-Slave interface on an VMEbus board. The interface is based on the SPC3-ASIC which handles the layer 1 / 2 of the PROFIBUS protocol (DIN 19245 / EN 50170) and the MC68331 processor. 64 kB dualport-RAM are used as data interface to the VMEbus.
With the PROFIBUS-DP-Slave firmware (DPS), the VME-PROF-S builds a independent arbitrary configurable DP-Slave interface. The slave is configured through the dualport-RAM. The configuration can be build with max. 32 configuration bytes and can use up to 244 input bytes and 244 output bytes. The total amount of input / output data can be 400 bytes.
Due to the arbitrary configuration the Slave can fit the requirements of the VMEbus system or the VME-PROF-S can be used to simulate other Slaves.

VME-PROF-S

lf you need to inquire or purchase ,please send the product models to my email or call medirectly .

sunny  He

[Email] sales@xiongbagk.cn

[Mobile] 86-18059884797

[WhatsApp] 86-18059884797

[Skype] sales@saulcontrol.com

VME-PROF-S PROFIBUS with PROFIBUS-DP-Slave state

VME-PROF-S VMEbus 68331 CPU, PROFIBUS DP-Slave 12 Mbit/sec, RS232, 6HE
VME-PROFS3 VMEbus 68331 CPU, PROFIBUS DP-Slave 12 Mbit/sec, RS232, 3HE
Other PROFIBUS products:
IPE VMEbus with 68040 CPU, 64 MHz, 8 MB RAM, IEC-1491 and PROFIBUS
DP-Master interface 3 Mbit/sec, RS232, 20 mA, 2 Memorycards
PCI-40 PC ISA-Slotcard with 68040 CPU, 64 MHz, 8 MB RAM, IEC-1491 and
PROFIBUS DP-Master interface 3 Mbit/sec
PCP-DP PC ISA-Slotcard with PROFIBUS DP-Master interface 3 Mbit/sec
VME-PROFI VMEbus PROFIBUS Interface 6 HE, 3 Mbit/s incl. PROFIBUS-DP-Master
Software
VME-PROFI3 VMEbus PROFIBUS- Interface 3 HE, 500 kbit/s incl. PROFIBUS DP-Master
Software
PMC-PROFI PMC Mezzanine Module with PROFIBUS DP-Master interface, 3 Mbit/s incl.
PROFIBUS-DP-Master Software
PCU PROFIBUS Control Unit with graphic display 320*240 pixel, 68331 CPU, 512
kB RAM, 2 MB Flash, Ethernet-Controller, OS9-Extended, TCP/IP, DPMaster Firmware
PST PROFIBUS DP Slave Terminal, display with 2 lines a 24 characters
Accessories:
PROFI-STV PROFIBUS Bus connector (9 pol. DSUB) with switchable terminating
resistors
PROF-KABEL PROFIBUS cable

· The device may only be used in subracks that meet the requirements of the following VMEbus standards: ANSI/IEEE STD1014-1987, IEC 821 and 297 [2]
· The device may only be switched on if installed properly.
· The device must be disconnected from the VCC power supply prior to connecting or disconnecting hardware interfaces.
· Handle with care! The device must be protected from electrostatic discharge (see EN 100015-1).
· This device uses, produces and may emit high-frequency signals. Operation of the device may be disturbed by strong high-frequency signals. The device has been designed by DMS for a high degree of electromagnetic compatibility, e.g. galvanic separated front interfaces, multi-layer technology, etc. have been incorporated in the design. Please make sure that the device is used in compliance with all applicable regulations regarding electromagnetic compatibility (EMC). See „Declaration of Conformity“ in the Preface chapter.