Description
Overview
Essential details:YNT512D Optical Bus Repeater for Max. 15 km (for V net) YOKOGAWA
GENERAL
The ProSafe-RS is a Safety Instrumented System that is certified by the German certification organization, Technische Überwachungs-Verein (TÜV) to meet Safety Integrity Level (SIL) 3 specified in IEC 61508. This GS explains the components and system specifications of the ProSafe-RS system.
COMPONENTS AND SOFTWARE
The ProSafe-RS system is composed of the Safety Control Station (SCS), the Safety Engineering PC (SENG). ProSafe-RS communicates with each of those equipment via V net control network and Ethernet.
The SCS performs safety control, and the SENG performs engineering and maintenance for the SCS. The ProSafeRS can be integrated with the CENTUM VP and CENTUM CS 3000 R3 (hereinafter, “VP/CS 3000”), an integrated production control system. The SCS can be operated and monitored by the HIS (human interface station) of the VP/CS 3000.
For specifications regarding the VP/CS 3000, refer to its general specifications.
For specifications regarding the system on Vnet/IP, refer to the general specifications (GS 32Q01B10-31E) for ProSafe-RS Safety Instrumented System Overview (for Vnet/IP).
Sales Manager: Manager He
E-mail number: sales@saulcontrol.com
skypel wechat: +86-18059884797
Mobile phonelwechat: +86-18059884797
QQ:3095989363
Safety Engineering PC (SENG)
To configure the ProSafe system, the CHS5100 Safety System Generation and Maintenance Package needs to be installed on a PC (IBM PC/AT-compatible computers). The SENG performs engineering and maintenance.
For details on the SENG’s functions, refer to the general specifications (GS 32Q04C10-31E) for the CHS5100 Safety System Generation and Maintenance Package.
Safety Control Station (SCS)
The SCS offers a safety control functions, the sequence-of-events-recorder (SOER) function, the VP/CS 3000 integration function, and the Modbus connection function which interfaces the SCS with another system.
The SCS consists of a safety control unit (CPU node) and safety node units (I/O node). There are two types of CPU nodes: a standard safety control unit and a wide range temperature safety control unit (equipped with a fan unit).
The CPU node can be connected with the I/O node via the ESB bus. I/O modules can be mounted both on the CPU node and I/O node alike.
Standard Type
SSC10S-S (model name): Safety Control Unit (for V net, Rack Mountable Type, Standard Type)
SSC10D-S (model name): Duplexed Safety Control Unit (for V net, Rack Mountable Type, Standard Type)
Wide Range Temperature Type
SSC10S-F (model name): Safety Control Unit (for V net, Rack Mountable Type, Wide Range Temperature Type)
SSC10D-F (model name): Duplexed Safety Control Unit
(for V net, Rack Mountable Type, Wide Range Temperature Type)
For details, refer to the general specifications “Safety Control Units, Duplexed Safety Control Units (for V net, Rack
Mountable Type)” (GS 32Q06D30-31E).
Basic Software
CFS1100 Safety Control Functions Package
For details of the CFS1100, refer to the general specifications “Safety Control Functions Package”
(GS 32Q03B20-31E).