Sale!

760-P1-G1-S1-LO-A20-R-E 760 Feeder Management Relay

The 760-P1-G1-S1-LO-A20-R model is one of the 760 Feeder Management Relays produced by GE Multilin. This model is labeled as a Feeder Distribution Management system. The part number is referred to as an order code and goes into detail as to what each feature of the system is. The features of this system are 1A phase current inputs, one 1A sensitive ground current input, a low-voltage control power at either 20 to 60 V DC or 20 to 48 V AC at 48 to 62 Hz, eight 4 to 20 mA analog outputs, a red LED for breaker closed indication, and 1A zero-sequence current inputs. One major downside of this specific relay system is that it is unsure as to what kind of display/Ethernet is used due to the lack of order character, and there is no harsh environmental protection.

Categories: ,

Description

Overview


Essential details:760-P1-G1-S1-LO-A20-R-E 760 Feeder Management Relay

760-P1-G1-S1-LO-A20-R Technical Specifications

Part Number 760-P1-G1-S1-LO-A20-R
Series 760 Feeder Management Relay
Manufacturer GE Multilin
Control Power 25 VA nominal, 35 VA max
Insulation Voltage 300 V
Overvoltage Category II
Pollution Degree II
Communications Protocol Modbus RTU or DNP 3.0
Data Logging Storage 2 to 16 events with 2048 to 256 samples of data respectively
Waveform Capture Sample Rate 16 per cycle

Product Description

The 760-P1-G1-S1-LO-A20-R model is one of the 760 Feeder Management Relays produced by GE Multilin. This model is labeled as a Feeder Distribution Management system. The part number is referred to as an order code and goes into detail as to what each feature of the system is. The features of this system are 1A phase current inputs, one 1A sensitive ground current input, a low-voltage control power at either 20 to 60 V DC or 20 to 48 V AC at 48 to 62 Hz, eight 4 to 20 mA analog outputs, a red LED for breaker closed indication, and 1A zero-sequence current inputs. One major downside of this specific relay system is that it is unsure as to what kind of display/Ethernet is used due to the lack of order character, and there is no harsh environmental protection. The 760-P1-G1-S1-LO-A20-R model has several different accessories, which include an SR three-inch COLLAR, 1A, and 5A phase CTs, and a DEMO metal carry case.

750-P5-G5-D5-HI-A20-R

lf you need to inquire or purchase ,please send the product models to my email or call medirectly .

sunny  He

[Email] sales@xiongbagk.cn

[Mobile] 86-18059884797

[WhatsApp] 86-18059884797

[Skype] sales@saulcontrol.com

760-P1-G1-S1-LO-A20-R-E 760 Feeder Management Relay

Product Description

On the front of the 760-P1-G1-S1-LO-A20-R model, there is a front panel interface. The front panel interface has LED status indicators, control keys, a liquid crystal display, and a programming port. The status indicators on the model are vital when indicating all of the potential alarm and status information to ensure that errors can be addressed quickly. The control keys are used to select the most suitable messaging to display measured values and enter setpoints.

For more information regarding the features of the 760-P1-G1-S1-LO-A20-R system, refer to all of the available GE Multilin documentation.

Frequently Asked Questions about 760-P1-G1-S1-LO-A20-R

What is the 760-P1-G1-S1-LO-A20-R?

The 760-P1-G1-S1-LO-A20-R model is a feeder distribution management system used for the management and the key protection and control of the distribution feeders. The model is easy to use and can provide comprehensive protection functions for feeders as well as back up protection for transformer and transmission lines in a drawout construction at a reduced cost.
What does the label state about the GE Feeder Management Relay and the part number for 760-P1-G1-S1-LO-A20-R?
The label for the relay specifies order codes and model numbers. For the GE Feeder Management Relay 760-P1-G1-S1-LO-A20-R label, can be found on the left side of the relay and the installed power supply’s operation range will be on the label.
Should the GE Feeder Management Relay for 760-P1-G1-S1-LO-A20-R be connected to the ground bus directly using the shortest path?
Yes, use the shortest practical path to the relay and connect the ground bus. A braided, copper, bonding cable that is shielding should be used to connect the ground bus. A belden catalog 8660 will work properly, as a minimum 96 strands of 34 AWG will work.
How should the GE Feeder Management Relay supervision circuit be wired for the 760-P1-G1-S1-LO-A20-R?
In the case for the GE Feeder Management Relay, the relays supervision circuit should be wired parallel to the trip contact. Just like the supervision of a close coil has the supervision circuit wired parellel with the close contact.