Actual unit speed is displayed on the front panels, of which there are three; one for each speed-sensing unit. It is through these panels that each unit is programmed, which can only be done with key lock access to prevent unauthorized programming or testing. This is also where the overspeed test frequency can be adjusted with a potentiometer. All three units are in the same, locked, NEMA 4X certified enclosure.
The 9905-750 system has a multitude of features and available functions, including:
- Remote reset
- Built-in self-test
- Functional status LED indicators (each speed-sensing unit has its own indicators)
- Alarm output
- Key lock to switch between PROGRAM and MONITOR modes
- Hot replacement modular design
The LED indicators will show if an MPU or its wiring has failed, if the corresponding speed-sensing unit has tripped (in which case there is also an alarm output), or if the unit’s CPU is not functioning normally.
The 9905-750 overspeed protection device has a trip speed set point range of 250 rpm to 25,000 rpm, a failed MPU set point range of 100 rpm to 25,000 rpm, and a failed MPU timeout range of 1 second to 533 minutes 20 seconds.