AAI141-H53/K4A00  Yokogawa Analog Input Module

AAI141-H53/K4A00  Yokogawa Analog Input Module

Manufacturers :Yokogawa
Model(s)  :AAI141-H53/K4A00
Additional Information :Analog Input Module
Estimated Shipping Size
Dimensions: 263 × 58 × 28mm
Weight:.4.3 kg
Country of Origin: United States of America

 

Categories: , SKU: AAI141-H53/K4A00 

Description

Overview


Essential details:AAI141-H53/K4A00  Yokogawa Analog Input Module

  • Manufacturer :Yokogawa
  • Product No. : AAI143-H53/K4A00
  • Product Type : Analog Input Module
  • H : With digital communication (HART protocol)
  • 5 : With no explosion protection
  • 3 : With ISA Standard G3 option and temperature (-20 to 70 °C) option
  • K4A00 : With KS Cable Interface Adapter (For connecting AEA4D Terminal Board) [Model: ATK4A-00]
  • Number of input channels : 16, isolated
  • Input signal : 4 to 20 mA
  • Allowable input current : 24 mA

ADV151-P63/D5A00

lf you need to inquire or purchase ,please send the product models to my email or call medirectly .

sunny  He

[Email] sales@xiongbagk.cn

[Mobile] 86-18059884797

[WhatsApp] 86-18059884797

[Skype] sales@saulcontrol.com

AAI141-H53/K4A00  Yokogawa Analog Input Module

  • Withstanding voltage : Between input and system: 1500 V AC, for 1 minute
  • Input resistance
    • Power ON : 270 ? (20 mA) to 350 ? (4 mA)
    • Power OFF : 500 k? or larger
  • Accuracy : ±16 µA
  • Data update period : 10 ms
  • Transmitter power supply : 19.0 V or higher (at 20 mA) 25.5 V or less (at 0 mA) (output current limit: 25 mA)
  • Setting of 2-wire or 4-wire transmitter : For each channel by setting pin
  • Drift due to ambient temperature change : ±16 µA/10 °C
  • Maximum current consumption : 230 mA (5 V DC), 540 mA (24 V DC)
  • External communication : Pressure clamp terminal, MIL connector cable, dedicated cable (KS1)
  • Weight : 0.3 Kg
  • Shipping Weight : 1.5 Kg