Description
Overview
Essential details:CLS208 Compact Loop System,Providing Powerful Controlin a ‘/s DIN Package
This manual describes how to install, set up, and operate a CLS204, CLS208 or CLS216 controller. Each chapter cov ers a different aspect of your control system and may apply to different users:
- Chapter 1: System Overview provides a component list and summary of features for the CLS200 series controllers.
- Chapter 2: Installation provides detailed instruc tions on installing the CLS200 series controller and its peripherals.
- Chapter 3: Using the CLS200 provides an overview of operator displays used for system monitoring and job selection.
- Chapter 4: Setup provides detailed descriptions of all menus and parameters for controller setup.
- Chapter 5: Extruder Control explains the addition al features of a CLS200 controller equipped with Ex truder Control Firmware.
- Chapter 6: Enhanced Features describes process variable retransmit, ratio, differential and cascade control features available with the enhanced features option.
- Chapter 7: Ramp/Soak explains how to set up and use the features of the ramp/soak option.
- Chapter 8: Tuning and Control describes available control algorithms and provides suggestions for appli cations.
- Chapter 9: Troubleshooting and Reconfiguring includes troubleshooting, upgrading and reconfigur ing procedures for technical personnel.
lf you need to inquire or purchase ,please send the product models to my email or call medirectly .
sunny He
[Email] sales@xiongbagk.cn
[Mobile] 86-18059884797
[WhatsApp] 86-18059884797
[Skype] sales@saulcontrol.com
CLS208 Compact Loop System,Providing Powerful Controlin a ‘/s DIN Package
The CLS200 series controllers provide 4, 8 or 16 fully inde pendent control loops. When used as a stand-alone control ler, you may operate the CLS200 via the two-line 16- character display and touch keypad. You can also use it as the key element in a computer-supervised data acquisition and control system; the CLS200 can be locally or remotely controlled via an EIA/TIA-232 or EIA/TIA-485 serial com munications interface. The CLS200 features include:
- Direct Connection of Mixed Thermocouple Sen sors: Connect most thermocouples to the controller with no hardware modifications. Thermocouple inputs feature reference junction compensation, lineariza tion, process variable offset calibration to correct for sensor inaccuracies, detection of broken, shorted or re versed thermocouples, and a choice of Fahrenheit or Celsius display.
- Accepts Resistive Temperature Detectors (RTDs): Use 3-wire, 100 Ω, platinum, 0.00385-curve sensors with two choices for range and precision of measurements. (To use this input, order a CLS204 or CLS208 controller with scaling resistors.)
- Automatic Scaling for Linear Analog Inputs: The CLS200 series automatically scales linear inputs used with industrial process sensors. Enter two points, and all input values are automatically scaled in your units. Scaling resistors must be installed.
- Dual Outputs: The CLS200 series includes both heat and cool control outputs for each loop. Independent control parameters are provided for each output.
- Independently Selectable Control and Output Modes: You can set each control output to on/off, time proportioning, Serial DAC (digital-to-analog convert er), or distributed zero crossing mode. Set up to two outputs per loop for on/off, P, PI or PID control with re verse or direct action.
- Control Outputs: Set high/low deviation and high/ low process limits to operate digital outputs as on/off control functions or alarms.
- Flexible Alarm Outputs: Independently set high/ low process alarms and a high/low deviation band alarm for each loop. Alarms can activate a digital out put by themselves, or they can be grouped with other alarms to activate an output.
- Global Alarm Output: When any alarm is triggered, the global alarm output is also triggered, and it stays on until you acknowledge it.