LDP1WC-47 LOW PRESSURE MONITOR

ECHOLINE’s Maintenance Mode feature prevents false alarms during system maintenance and balancing.
A customer defined time delay prevents false trips which can cause system shutdowns. “ECHO” (Electronic Circuit Health Output) diagnostics alert the user to loss of external power or internal electronics failure.
Four ECHOLINE® units fit into the space of one oldfashioned gauge/switch.

Categories: ,

Description

Overview


Essential details:LDP1WC-47 LOW PRESSURE MONITOR

ECHOLINE®
was designed in cooperation with a leading semiconductor manufacturer to prevent costly system shutdowns and reduce maintenance costs associated with low pressure monitoring of gas cabinet exhaust systems.
ECHOLINE’s Maintenance Mode feature prevents false alarms during system maintenance and balancing.
A customer defined time delay prevents false trips which can cause system shutdowns. “ECHO” (Electronic Circuit Health Output) diagnostics alert the user to loss of external power or internal electronics failure.
Four ECHOLINE® units fit into the space of one oldfashioned gauge/switch.

Operation
High and low limit alarms are independently set from the front panel. In normal operation, the LED display will indicate the sensed pressure and the High Limit/Low Limit LED status indicators will be green. When a preset limit is exceeded, the LED signals an alarm condition by turning red. After a customer selected time delay, the electromechanical relay contacts will be latched open and the LED display will flash the process pressure once every second. Manually depressing the reset button will cause the relay contacts to close if and when the process pressure is within set limits.
Maintenance Mode
The “Maintenance Mode” option is a unique and convenient safety feature which allows the user to widen the alarm set points during system maintenance. By closing terminal circuits 3 and 4, using a key switch or password protected computer, the user can expand the limits to 5% and 95% of the range to continue monitoring and prevent false trips. Opening terminal circuits 3 and 4 immediately returns the set points to the previous settings.
Time Delay ECHOLINE®
includes an adjustable “stand alone” time delay to prevent intermittent tripping due to brief transient upsets. When the unit senses a pressure outside the limits, the status LED will immediately turn red, but the relay will not open for a pre-selected time delay. The time delay will reset to zero if the process pressure returns to within the limits during the transient conditions. This feature provides a degree of “fault tolerance” for exhaust flow interlock applications. The time delay is field settable through a jumper located on the rear of the enclosure for 1, 10, 20 or 30 seconds.

LDP1WC-47

lf you need to inquire or purchase ,please send the product models to my email or call medirectly .

sunny  He

[Email] sales@xiongbagk.cn

[Mobile] 86-18059884797

[WhatsApp] 86-18059884797

[Skype] sales@saulcontrol.com

LDP1WC-47 LOW PRESSURE MONITOR

When Used To Provide Safety Interlock, Monitor Ventilation Or Optimize Exhaust, ECHOLINE®
Features:
• Discrete all analog electronic components – no microprocessor
• Self-monitoring “ECHO” diagnostics
• Complies with the requirements of UL 991 and UL 508
• Fault tolerant design
• Maintenance mode
• User selected time delay
• Convenient interfacing with facility alarm system
When Used To Monitor Non- Critical Ventilation, ECHOLINE® Features:
• Maintenance mode to prevent false trips during ventilation system balancing
• Optional non-latching relay
• Bright LED display of process pressure

Indicating Pressure Ranges 0.2 to 20” WC (see model chart)
Display 3½ digit, 0.30” high red LED
Alarm Set Point Range Independently set high and low limits, 5 to 95% of
indicating range
Reset Alarm condition will remain until front panel reset button
is pressed, and pressure is within limits
Calibration Field adjustable zero via front panel screw adjustment
Accuracy 1% of range @ 20° C
Switch and ECHO Outputs Electro-mechanical relay, SPDT, Form A Dry Contacts
Relay Rating 1.0A @ 30 VDC, resistive
Status LEDs Green in normal state, red in alarm state
Time Delay 1, 10, 20, 30 seconds. Factory set at 10 seconds. Changeable
via rear panel jumper.
Analog Output (optional) 0-10 VDC or 4-20 mA, non-isolated, current sinking.
Maintenance Mode feature disabled.
Overpressure ± 14.5 psi (8” WC and above), ± 80” WC (under 8” WC)
Pressure Connection Push-to-connect fitting(s) for 0.25” O.D. tubing or dual
barbed fitting for 0.170” I.D. hose
Media Dry air, or inert non-conductive gas
Operating Ambient Temperature 0 to 40°C
Enclosure 1/16th DIN 43700, panel mounted polycarbonate, plastic
Wiring Plugable terminal block, 18-26 AWG, DSub (9 pin) connector
Weight 7 oz (200 g) maximum
Power 12-24 VDC, 1.4 Watts