Sale!

MTL4544AS MTL Analogue Input – 2-wire transmitters

MTL4544AS MTL Analogue Input – 2-wire transmitters

Manufacturers :MTL
Model(s)  :MTL4544AS
Additional Information :Analogue Input – 2-wire transmitters
Estimated Shipping Size
Dimensions: 263 × 58 × 28mm
Weight:.4.3 kg
Country of Origin: United States of America

 

Categories: , SKU: MTL4544AS

Description

Overview


Essential details:MTL4544AS MTL Analogue Input – 2-wire transmitters

The MTLx544A provides an input for separately powered 4/20mA transmitters and also allows bi–directional transmission of HART communication signals superimposed on the 4/20mA loop current, so that the transmitter can be interrogated either from the operator station or by a hand-held communicator (HHC). Alternatively, the MTLx544AS acts as a current sink for a safe-area connection rather than driving a current into the load.

MTL4544AS

lf you need to inquire or purchase ,please send the product models to my email or call medirectly .

sunny  He

[Email] sales@saulcontrol.com

[Mobile] 86-18059884797

[WhatsApp] 86-18059884797

[Skype] sales@saulcontrol.com

MTL4544AS MTL Analogue Input – 2-wire transmitters

Number of channels
Two
Location of transmitter
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div.1, Group A, hazardous loc ation
Hazardous area input
Signal range: 4 to 20mA
Under/over-range: 1.0 to 21.5mA
Input impedance for HART signals
at terminals 1, 2 and 4, 5: > 230Ω
Maximum input volt drop
at terminals 1, 2 and 4, 5: < 6.6V
i.e. a transmitter load of 330Ω at 20mA
Safe-area output
Signal range: 4 to 20mA
Under/over-range: 1.0 to 21.5mA
Safe-area load resistance (MTL5544A)
Conventional transmitters: 0 to 360Ω
Smart transmitters: 250Ω ±10%
Safe-area load (MTL5544AS)
Current sink: 600Ω max.
Maximum voltage source: 24V DC
Safe-area circuit output resistance: > 1MΩ
Safe–area circuit ripple
< 50µA peak-to-peak up to 80kHz
Transfer accuracy at 20°C
Better than 20µA
Temperature drift
< 1µA/°C
Response time
Settles within 200µA of final value after 20ms
Communications supported
HART
LED indicator
Green: power indication
Power requirement (with 20mA signal)
70mA at 24V
85mA at 20V
50mA at 35V