Essential details:RED670 1MRK004810-KG Line differential protection
lf you need to inquire or purchase ,please send the product models to my email or call medirectly .
sunny He
[Email] sales@xiongbagk.cn
[Mobile] 86-18059884797
[WhatsApp] 86-18059884797
[Skype] sales@saulcontrol.com
RED670 1MRK004810-KG Line differential protection
High set instantaneous phase and earth overcurrent, four step directional or un-directional delayed phase and earth overcurrent, thermal overload and two step under- and overvoltage functions are examples of the available functions allowing the user to fulfill any application requirement.
The IED can also be provided with a full control and interlocking functionality including co-operation with the synchronism check function to allow integration of the main or back-up control.
Disturbance recording and fault locator are available to allow independent post-fault analysis after primary disturbances. The
Disturbance recorder will also show remote station currents, as received to this IED, time compensated with measure communication time.
Out of Step function is available to separate power system sections close to electrical centre at occurring out of step.
The IED can be used in applications with IEC 61850-9-2LE process bus with up to six merging units (MU) depending on other functionality included in the IED.
Each MU has eight analogue channels, normally four currents and four voltages. Conventional and Merging Unit channels can be mixed freely in the application.
The logic is prepared with a graphical tool. The advanced logic capability allows special applications such as automatic opening of disconnectors in multi-breaker arrangements, closing of breaker rings, load transfer logics etc. The graphical configuration tool ensures simple and fast testing and commissioning.
A loop testing function allows complete testing including remote end IED when local IED is set in test mode.