REJ603Â Self-Powered Feeder Protection
The combined overcurrent and earth-fault relay is a secondary relay to be connected to the current transformers of the protected object. Apart from the measurement (inputs), the relay derives energy required for its own operation and tripping of circuit breaker from the current transformers. There are two LED’s on the front panel. When minimum current required for operation is available the green ‘Ready’ LED glows indicating the relay is in operation. On detection of a fault the relay trips the circuit breaker in accordance with the settings. The relay also does internal health check at regular interval and intimates user in case of any internal relay failure. The internal relay failure is indicated by red ‘IRF’ LED. .
When the phase current exceeds the set operate time at definite time operation or the calculated operate time at inverse time operation elapses, the overcurrent unit operates. In the same way the high-set stage I>> of the overcurrent unit operates when the set operate time elapses.
When the earth-fault current exceeds the set operate time at definite time operation or the calculated operate time at inverse time operation elapses, the earth-fault unit operates. In the same way the high-set stage I0>> of the earth-fault unit operates when the set operate time elapses.