Sale!

TAP-210DG/3 DEIF Transducers for AC measurement

TAP-210DG/3 DEIF Transducers for AC measurement

Manufacturers :DEIF
Model(s)  :TAP-210DG/3
Additional Information :Transducers for AC measurement
Estimated Shipping Size
Dimensions: 263 × 58 × 28mm
Weight:.4.3 kg
Country of Origin: United States of America

 

Categories: , SKU: TAP-210DG/3

Description

Overview


Essential details:TAP-210DG/3 DEIF Transducers for AC measurement

 Measurement of:
watt, var, frequency, phase angle, voltage, current
 Accuracy class 0.5
 For mounting on DIN rail
 Compact design
 Aux. voltage: 57.7…440V AC or 24…220V DC
 According to IEC 688

Measuring principle Time-Division-Multiplication (TDM) RMS measurement
Measuring voltage (Unom) 57.7..440V AC ±20% (0..120% Unom with separate Uaux), ( 0.5VA per phase)
Measuring current (Inom) 0.5..10A AC. Measuring range: 0..120% Inom ( 0.3VA per phase)
Measuring range 0..Qnom / -Qnom..0..+Qnom
Measuring frequency 45..65Hz (300..500Hz)
Overloads Voltages 1.2 x Unom, cont. / 2 x Unom for 10 s
Overloads Currents 2 x Inom, cont. / 10 x Inom for 10 s (max. 75A) / 40 x Inom for 1 sec (max. 300A)
Output (0..100%) 0..1mA, 0..5mA, 0..10mA, 0..20mA, 0..1V, 0..10V
Output (20..100%) 0.2..1mA, 1..5mA, 2..10mA, 4..20mA, 0.2..1V, 2..10V
Output (-100%..0..+100%) -1..0..+1mA, -5..0..+5mA, -10..0..+10mA, -20..0..+20mA, -1..0..+1V, -10..0..+10V
Output loads Current Output: max. 15V, voltage Output: max. 20mA
Accuracy Class 0.5 (-10..15..30..55°C) according to IEC 688
Response time/ripple <150 ms / 1%pp according to IEC 688
out / Uaux / faux / Rload Max. 0.1%/ 10% Uaux / 0.1%/45..65Hz / 0.1%/ Rload-max.
Temperature coefficient Typically 0.15% per 10°C. Max. 0.2% per 10°C
Ambient temperature -10..+55°C (nominal). -25..+70°C (operating). -40..+70°C (storage)
Auxiliary supply (Uaux) (45..65Hz) 57.7 – 63.5 – 100 – 110 – 120 – 127 – 220 – 230 – 240 – 380 – 415 – 440V AC ±20% (3.5VA)
Test voltage 2000V – 50Hz – 1 min.
EMC According to EN 50081-1/2, EN 50082-1/2, SS4361503 (PL4), IEC 255-4 (class 3). CE marked
Climate Class HSE, according to DIN 40040
Protection Case: IP52. Terminals: IP20. According to IEC 529 and EN 60529
Terminals Screw Terminals. Multi-stranded: 2.5 mm² / single-stranded: 4.0 mm²

TAP-210DG/3

lf you need to inquire or purchase ,please send the product models to my email or call medirectly .

sunny  He

[Email] sales@xiongbagk.cn

[Mobile] 86-18059884797

[WhatsApp] 86-18059884797

[Skype] sales@saulcontrol.com

TAP-210DG/3 DEIF Transducers for AC measurement

Measuring principle Zero crossing detection. NOTE: Output proportional to phase angle ()
Measuring voltage (Unom) 57.7..440V AC ±20% ( 0.5VA)
Measuring current (Inom) -/1A – -/5A. Measuring range: 20..120% Inom (class 0.5) 5..20% (class 1) ( 0.3VA)
Measuring range 0.5 cap…1..0.5 ind. / 0.7 cap…1..0.3 ind. / 0..1 cap. / 0..1 ind.
Measuring frequency 45..65Hz (300..500Hz)
Overloads Voltages 1.2 x Unom, cont. / 2 x Unom for 10 s
Overloads Currents 2 x Inom, cont. / 10 x Inom for 10 s (max. 75A) / 40 x Inom for 1 sec (max. 300A)
Output (0..100%) 0..1mA, 0..5mA, 0..10mA, 0..20mA, 0..1V, 0..10V
Output (20..100%) 0.2..1mA, 1..5mA, 2..10mA, 4..20mA, 0.2..1V, 2..10V. With separate aux. voltage
Output (-100%..0..+100%) -1..0..+1mA, -5..0..+5mA, -10..0..+10mA, -20..0..+20mA, -1..0..+1V, -10..0..+10V
Output loads Current Output: max. 15V, voltage Output: max. 20mA
Accuracy Class 0.5 (-10..15..30..55°C) according to IEC 688
Response time/ripple <300 ms / 1%pp according to IEC 688
out / Uaux / faux / Rload Max. 0.1%/ 10% Uaux / 0.1%/45..65Hz / 0.1%/ Rload-max.
Temperature coefficient Typically 0.15% per 10°C. Max. 0.2% per 10°C
Ambient temperature -10..+55°C (nominal). -25..+70°C (operating). -40..+70°C (storage)
Auxiliary supply (Uaux) (45..65Hz) 57.7 – 63.5 – 100 – 110 – 120 – 127 – 220 – 230 – 240 – 380 – 415 – 440V AC ±20% (2VA)
Test voltage 2000V – 50Hz – 1 min.
EMC According to EN 50081-1/2, EN 50082-1/2, SS4361503 (PL4), IEC 255-4 (class 3). CE marked
Climate Class HSE, according to DIN 40040
Protection Case: IP52. Terminals: IP20. According to IEC 529 and EN 60529
Terminals Screw Terminals. Multi-stranded: 2.5 mm² / single-stranded: 4.0 mm²